Recall

Aginode LANmark-OF Micro-Bundle Universal 12x Multimode Cable Recall (October 2026)

Testing has indicated that the product failed to achieve its declared reaction to fire pe….

WhatAginode LANmark-OF Micro-Bundle Universal 12x Multimode Cable
BrandAginode
The hazardTesting has indicated that the product failed to achieve its declared reaction to fire performance.
Product typeConstruction Products - Cable/Wire Conduit/Ducting/Raceways
Made inBelgium
Issued byOffice for Product Safety and Standards
Recall date2026-10-13 (notice 2507-0172)

What was recalled

Internet LAN network cable.

Why it was recalled

Testing has indicated that the product failed to achieve its declared reaction to fire performance. The reaction to fire performance declared in the Manufacturers Declaration of Performance is class B2ca-s1a,d0,a1. Independent testing has indicated that the performance achieved by the product was Fca.

The product therefore may not perform to the to the declared reaction to fire performance.

What to do

Aginode Belgium have withdrawn this batch of product from the market. Aginode Belgium have recalled the product from the supply chain in the UK and issued a warning notice to end users that the product may not meet its declared performance.

The potential impact of lower performance of a product in relation to reaction to fire and building safety will vary on a project-by-project basis and will depend on factors unique to each building.

Aginode have written to customers in the UK advising them that those who selected the identified product relying upon the declared reaction to fire Class of B2ca-s1a,d0,a1 are warned that the actual performance of this product may not achieve B2ca-s1a,d0,a1 classification and they should consider whether the lack of performance to Class B2ca-s1a,d0,a1 is material to the fire performance of the setting it is used in.

Aginode have written to customers in the UK advising those responsible for buildings to consider whether this shortfall in performance affects the fire safety of the environment in which the product is used.

Additional information

PSD notification number: 2507-0172

Notified by: Office for Product Safety and Standards

Source: the official OPSS product recall notice, published 2026-10-13. Every fact on this page comes from that notice — if anything here disagrees with it, the notice wins.

Contains public sector information licensed under the Open Government Licence v3.0.